Evaporative cooler

(Redirected from Air coolers)

An evaporative cooler (also known as evaporative air conditioner, swamp cooler, swamp box, desert cooler and wet air cooler) is a device that cools air through the evaporation of water. Evaporative cooling differs from other air conditioning systems, which use vapor-compression or absorption refrigeration cycles. Evaporative cooling exploits the fact that water will absorb a relatively large amount of heat in order to evaporate (that is, it has a large enthalpy of vaporization). The temperature of dry air can be dropped significantly through the phase transition of liquid water to water vapor (evaporation). This can cool air using much less energy than refrigeration. In extremely dry climates, evaporative cooling of air has the added benefit of conditioning the air with more moisture for the comfort of building occupants.

An Egyptian qullah, set in drafts to cool interiors. Porous pottery and coarse cloth maximize the area for evaporation.

The cooling potential for evaporative cooling is dependent on the wet-bulb depression, the difference between dry-bulb temperature and wet-bulb temperature (see relative humidity). In arid climates, evaporative cooling can reduce energy consumption and total equipment for conditioning as an alternative to compressor-based cooling. In climates not considered arid, indirect evaporative cooling can still take advantage of the evaporative cooling process without increasing humidity. Passive evaporative cooling strategies can offer the same benefits as mechanical evaporative cooling systems without the complexity of equipment and ductwork.

History

edit

An earlier form of evaporative cooling, the windcatcher, was first used in ancient Egypt and Persia thousands of years ago in the form of wind shafts on the roof. They caught the wind, passed it over subterranean water in a qanat and discharged the cooled air into the building. Modern Iranians have widely adopted powered evaporative coolers (coolere âbi).[1]

The evaporative cooler was the subject of numerous US patents in the 20th century; many of these, starting in 1906,[2] suggested or assumed the use of excelsior (wood wool) pads as the elements to bring a large volume of water in contact with moving air to allow evaporation to occur. A typical design, as shown in a 1945 patent, includes a water reservoir (usually with level controlled by a float valve), a pump to circulate water over the excelsior pads and a centrifugal fan to draw air through the pads and into the house.[3] This design and this material remain dominant in evaporative coolers in the American Southwest, where they are also used to increase humidity.[4] In the United States, the use of the term swamp cooler may be due to the odor of algae produced by early units.[5]

Externally mounted evaporative cooling devices (car coolers) were used in some automobiles to cool interior air—often as aftermarket accessories[6]—until modern vapor-compression air conditioning became widely available.

Passive evaporative cooling techniques in buildings have been a feature of desert architecture for centuries, but Western acceptance, study, innovation, and commercial application are all relatively recent. In 1974, William H. Goettl noticed how evaporative cooling technology works in arid climates, speculated that a combination unit could be more effective, and invented the "High Efficiency Astro Air Piggyback System", a combination refrigeration and evaporative cooling air conditioner. In 1986, University of Arizona researchers built a passive evaporative cooling tower, and performance data from this experimental facility in Tucson, Arizona became the foundation of evaporative cooling tower design guidelines.[7]

Physical principles

edit
 
A traditional air cooler in Mirzapur, Uttar Pradesh, India

Evaporative coolers lower the temperature of air using the principle of evaporative cooling, unlike typical air conditioning systems which use vapor-compression refrigeration or absorption refrigeration. Evaporative cooling is the conversion of liquid water into vapor using the thermal energy in the air, resulting in a lower air temperature. The energy needed to evaporate the water is taken from the air in the form of sensible heat, which affects the temperature of the air, and converted into latent heat, the energy present in the water vapor component of the air, whilst the air remains at a constant enthalpy value. This conversion of sensible heat to latent heat is known as an isenthalpic process because it occurs at a constant enthalpy value. Evaporative cooling therefore causes a drop in the temperature of air proportional to the sensible heat drop and an increase in humidity proportional to the latent heat gain. Evaporative cooling can be visualized using a psychrometric chart by finding the initial air condition and moving along a line of constant enthalpy toward a state of higher humidity.[8]

A simple example of natural evaporative cooling is perspiration, or sweat, secreted by the body, evaporation of which cools the body. The amount of heat transfer depends on the evaporation rate, however for each kilogram of water vaporized 2,257 kJ of energy (about 890 BTU per pound of pure water, at 95 °F (35 °C)) are transferred. The evaporation rate depends on the temperature and humidity of the air, which is why sweat accumulates more on humid days, as it does not evaporate fast enough.

Vapor-compression refrigeration uses evaporative cooling, but the evaporated vapor is within a sealed system, and is then compressed ready to evaporate again, using energy to do so. A simple evaporative cooler's water is evaporated into the environment, and not recovered. In an interior space cooling unit, the evaporated water is introduced into the space along with the now-cooled air; in an evaporative tower the evaporated water is carried off in the airflow exhaust.

Other types of phase-change cooling

edit

A closely related process, sublimation cooling, differs from evaporative cooling in that a phase transition from solid to vapor, rather than liquid to vapor, occurs.

Sublimation cooling has been observed to operate on a planetary scale on the planetoid Pluto, where it has been called an anti-greenhouse effect.

Another application of a phase change to cooling is the "self-refrigerating" beverage can. A separate compartment inside the can contains a desiccant and a liquid. Just before drinking, a tab is pulled so that the desiccant comes into contact with the liquid and dissolves. As it does so, it absorbs an amount of heat energy called the latent heat of fusion. Evaporative cooling works with the phase change of liquid into vapor and the latent heat of vaporization, but the self-cooling can uses a change from solid to liquid, and the latent heat of fusion, to achieve the same result.

Applications

edit

Before the advent of modern refrigeration, evaporative cooling was used for millennia, for instance in qanats, windcatchers, and mashrabiyas. A porous earthenware vessel would cool water by evaporation through its walls; frescoes from about 2500 BCE show slaves fanning jars of water to cool rooms[citation needed]. Alternatively, a bowl filled with milk or butter could be placed in another bowl filled with water, all being covered with a wet cloth resting in the water, to keep the milk or butter as fresh as possible (see zeer, botijo and Coolgardie safe).[9]

 
Ancient Persian passive design taking advantage of evaporative cooling
 
California ranch house with evaporative cooler box on roof ridgeline on right

Evaporative cooling is a common form of cooling buildings for thermal comfort since it is relatively cheap and requires less energy than other forms of cooling.

 
Psychrometric chart example of Salt Lake City

The figure showing the Salt Lake City weather data represents the typical summer climate (June to September). The colored lines illustrate the potential of direct and indirect evaporative cooling strategies to expand the comfort range in summer time. It is mainly explained by the combination of a higher air speed on one hand and elevated indoor humidity when the region permits the direct evaporative cooling strategy on the other hand. Evaporative cooling strategies that involve the humidification of the air should be implemented in dry condition where the increase in moisture content stays below recommendations for occupant's comfort and indoor air quality. Passive cooling towers lack the control that traditional HVAC systems offer to occupants. However, the additional air movement provided into the space can improve occupant comfort.

Evaporative cooling is most effective when the relative humidity is on the low side, limiting its popularity to dry climates. Evaporative cooling raises the internal humidity level significantly, which desert inhabitants may appreciate as the moist air re-hydrates dry skin and sinuses. Therefore, assessing typical climate data is an essential procedure to determine the potential of evaporative cooling strategies for a building. The three most important climate considerations are dry-bulb temperature, wet-bulb temperature, and wet-bulb depression during a typical summer day. It is important to determine if the wet-bulb depression can provide sufficient cooling during the summer day. By subtracting the wet-bulb depression from the outside dry-bulb temperature, one can estimate the approximate air temperature leaving the evaporative cooler. It is important to consider that the ability for the exterior dry-bulb temperature to reach the wet-bulb temperature depends on the saturation efficiency. A general recommendation for applying direct evaporative cooling is to implement it in places where the wet-bulb temperature of the outdoor air does not exceed 22 °C (72 °F).[7] However, in the example of Salt Lake City, the upper limit for the direct evaporative cooling on psychrometric chart is 20 °C (68 °F). Despite the lower temperature, evaporative cooling is suitable for similar climates to Salt Lake City.

Evaporative cooling is especially well suited for climates where the air is hot and humidity is low. In the United States, the western and mountain states are good locations, with evaporative coolers prevalent in cities like Albuquerque, Denver, El Paso, Fresno, Salt Lake City, and Tucson. Evaporative air conditioning is also popular and well-suited to the southern (temperate) part of Australia. In dry, arid climates, the installation and operating cost of an evaporative cooler can be much lower than that of refrigerative air conditioning, often by 80% or so. However, evaporative cooling and vapor-compression air conditioning are sometimes used in combination to yield optimal cooling results. Some evaporative coolers may also serve as humidifiers in the heating season. In regions that are mostly arid, short periods of high humidity may prevent evaporative cooling from being an effective cooling strategy. An example of this event is the monsoon season in New Mexico and central and southern Arizona in July and August.

In locations with moderate humidity there are many cost-effective uses for evaporative cooling, in addition to their widespread use in dry climates. For example, industrial plants, commercial kitchens, laundries, dry cleaners, greenhouses, spot cooling (loading docks, warehouses, factories, construction sites, athletic events, workshops, garages, and kennels) and confinement farming (poultry ranches, hog, and dairy) often employ evaporative cooling. In highly humid climates, evaporative cooling may have little thermal comfort benefit beyond the increased ventilation and air movement it provides.

Other examples

edit

Trees transpire large amounts of water through pores in their leaves called stomata, and through this process of evaporative cooling, forests interact with climate at local and global scales.[10] Simple evaporative cooling devices such as evaporative cooling chambers (ECCs) and clay pot coolers, or pot-in-pot refrigerators, are simple and inexpensive ways to keep vegetables fresh without the use of electricity. Several hot and dry regions throughout the world could potentially benefit from evaporative cooling, including North Africa, the Sahel region of Africa, the Horn of Africa, southern Africa, the Middle East, arid regions of South Asia, and Australia. Benefits of evaporative cooling chambers for many rural communities in these regions include reduced post-harvest loss, less time spent traveling to the market, monetary savings, and increased availability of vegetables for consumption.[11][12]

Evaporative cooling is commonly used in cryogenic applications. The vapor above a reservoir of cryogenic liquid is pumped away, and the liquid continuously evaporates as long as the liquid's vapor pressure is significant. Evaporative cooling of ordinary helium forms a 1-K pot, which can cool to at least 1.2 K. Evaporative cooling of helium-3 can provide temperatures below 300 mK. These techniques can be used to make cryocoolers, or as components of lower-temperature cryostats such as dilution refrigerators. As the temperature decreases, the vapor pressure of the liquid also falls, and cooling becomes less effective. This sets a lower limit to the temperature attainable with a given liquid.

Evaporative cooling is also the last cooling step in order to reach the ultra-low temperatures required for Bose–Einstein condensation (BEC). Here, so-called forced evaporative cooling is used to selectively remove high-energetic ("hot") atoms from an atom cloud until the remaining cloud is cooled below the BEC transition temperature. For a cloud of 1 million alkali atoms, this temperature is about 1μK.

Although robotic spacecraft use thermal radiation almost exclusively, many crewed spacecraft have short missions that permit open-cycle evaporative cooling. Examples include the Space Shuttle, the Apollo command and service module (CSM), lunar module and portable life support system. The Apollo CSM and the Space Shuttle also had radiators, and the Shuttle could evaporate ammonia as well as water. The Apollo spacecraft used sublimators, compact and largely passive devices that dump waste heat in water vapor (steam) that is vented to space.[citation needed] When liquid water is exposed to vacuum it boils vigorously, carrying away enough heat to freeze the remainder to ice that covers the sublimator and automatically regulates the feedwater flow depending on the heat load. The water expended is often available in surplus from the fuel cells used by many crewed spacecraft to produce electricity.

Designs

edit
 
Evaporative cooler illustration

Most designs take advantage of the fact that water has one of the highest known enthalpy of vaporization (latent heat of vaporization) values of any common substance. Because of this, evaporative coolers use only a fraction of the energy of vapor-compression or absorption air conditioning systems. Except in very dry climates, the single-stage (direct) cooler can increase relative humidity (RH) to a level that makes occupants uncomfortable. Indirect and two-stage evaporative coolers keep the RH lower.

Direct evaporative cooling

edit
 
Direct evaporative cooling

Direct evaporative cooling (open circuit) is used to lower the temperature and increase the humidity of air by using latent heat of evaporation, changing liquid water to water vapor. In this process, the energy in the air does not change. Warm dry air is changed to cool moist air. The heat of the outside air is used to evaporate water. The RH increases to 70 to 90% which reduces the cooling effect of human perspiration. The moist air has to be continually released to outside or else the air becomes saturated and evaporation stops.

A mechanical direct evaporative cooler unit uses a fan to draw air through a wetted membrane, or pad, which provides a large surface area for the evaporation of water into the air. Water is sprayed at the top of the pad so it can drip down into the membrane and continually keep the membrane saturated. Any excess water that drips out from the bottom of the membrane is collected in a pan and recirculated to the top. Single-stage direct evaporative coolers are typically small in size as they only consist of the membrane, water pump, and centrifugal fan. The mineral content of the municipal water supply will cause scaling on the membrane, which will lead to clogging over the life of the membrane. Depending on this mineral content and the evaporation rate, regular cleaning and maintenance are required to ensure optimal performance. Generally, supply air from the single-stage evaporative cooler will need to be exhausted directly (one-through flow) as with direct evaporative cooling. A few design solutions have been conceived to utilize the energy in the air, like directing the exhaust air through two sheets of double glazed windows, thus reducing the solar energy absorbed through the glazing.[13] Compared to energy required to achieve the equivalent cooling load with a compressor, single stage evaporative coolers consume less energy.[7]

Passive direct evaporative cooling can occur anywhere that the evaporatively cooled water can cool a space without the assistance of a fan. This can be achieved through the use of fountains or more architectural designs such as the evaporative downdraft cooling tower, also called a "passive cooling tower". The passive cooling tower design allows outside air to flow in through the top of a tower that is constructed within or next to the building. The outside air comes in contact with water inside the tower either through a wetted membrane or a mister. As water evaporates in the outside air, the air becomes cooler and less buoyant and creates a downward flow in the tower. At the bottom of the tower, an outlet allows the cooler air into the interior. Similar to mechanical evaporative coolers, towers can be an attractive low-energy solution for hot and dry climate as they only require a water pump to raise water to the top of the tower.[14] Energy savings from using a passive direct evaporating cooling strategy depends on the climate and heat load. For arid climates with a great wet-bulb depression, cooling towers can provide enough cooling during summer design conditions to be net zero. For example, a 371 m2 (4,000 ft2) retail store in Tucson, Arizona with a sensible heat gain of 29.3 kJ/h (100,000 Btu/h) can be cooled entirely by two passive cooling towers providing 11890 m3/h (7,000 cfm) each.[15]

For the Zion National Park visitors' center, which uses two passive cooling towers, the cooling energy intensity was 14.5 MJ/m2 (1.28 kBtu/ft2;), which was 77% less than a typical building in the western United States that uses 62.5 MJ/m2 (5.5 kBtu/ft2).[16] A study of field performance results in Kuwait revealed that power requirements for an evaporative cooler are approximately 75% less than the power requirements for a conventional packaged unit air-conditioner.[17]

Indirect evaporative cooling

edit
 
The process of indirect evaporative cooling

Indirect evaporative cooling (closed circuit) is a cooling process that uses direct evaporative cooling in addition to some heat exchanger to transfer the cool energy to the supply air. The cooled moist air from the direct evaporative cooling process never comes in direct contact with the conditioned supply air. The moist air stream is released outside or used to cool other external devices such as solar cells which are more efficient if kept cool. This is done to avoid excess humidity in enclosed spaces, which is not appropriate for residential systems.

Maisotsenko cycle

edit

Indirect cooler manufacturer uses the Maisotsenko cycle (M-Cycle), named after inventor and Professor Dr. Valeriy Maisotsenko, employs an iterative (multi-step) heat exchanger made of a thin recyclable membrane that can reduce the temperature of product air to below the wet-bulb temperature, and can approach the dew point.[18] Testing by the US Department of Energy found that a hybrid M-Cycle combined with a standard compression refrigeration system significantly improved efficiency by between 150 and 400% but was only capable of doing so in the dry western half of the US, and did not recommend being used in the much more humid eastern half of the US. The evaluation found that the system water consumption of 2–3 gallons per cooling ton (12,000 BTUs) was roughly equal in efficiency to the water consumption of new high efficiency power plants. This means the higher efficiency can be utilized to reduce load on the grid without requiring any additional water, and may actually reduce water usage if the source of the power does not have a high efficiency cooling system.[19]

An M-Cycle based system built by Coolerado is currently being used to cool the Data Center for NASA's National Snow and Ice Data Center (NSIDC). The facility is air cooled below 70 degrees Fahrenheit and uses the Coolerado system above that temperature. This is possible because the air handler for the system uses fresh outside air, which allows it to automatically use cool outside ambient air when conditions allow. This avoids running the refrigeration system when unnecessary. It is powered by a solar panel array which also serves as secondary power in case of main power loss.[20]

The system has very high efficiency but, like other evaporative cooling systems, is constrained by the ambient humidity levels, which has limited its adoption for residential use. It may be used as supplementary cooling during times of extreme heat without placing significant additional burden on electrical infrastructure. If a location has excess water supplies or excess desalination capacity it can be used to reduce excessive electrical demand by utilizing water in affordable M-Cycle units. Due to high costs of conventional air conditioning units and extreme limitations of many electrical utility systems, M-Cycle units may be the only appropriate cooling systems suitable for impoverished areas during times of extremely high temperature and high electrical demand. In developed areas, they may serve as supplemental backup systems in case of electrical overload, and can be used to boost efficiency of existing conventional systems.

The M-Cycle is not limited to cooling systems and can be applied to various technologies from Stirling engines to Atmospheric water generators. For cooling applications it can be used in both cross flow and counterflow configurations. Counterflow was found to obtain lower temperatures more suitable for home cooling, but cross flow was found to have a higher coefficient of performance (COP), and is therefore better for large industrial installations.

Unlike traditional refrigeration techniques, the COP of small systems remains high, as they do not require lift pumps or other equipment required for cooling towers. A 1.5 ton/4.4 kW cooling system requires just 200 watts for operation of the fan, giving a COP of 26.4 and an EER rating of 90. This does not take into account the energy required to purify or deliver the water, and is strictly the power required to run the device once water is supplied. Though desalination of water also presents a cost, the latent heat of vaporization of water is nearly 100 times higher than the energy required to purify the water itself. Furthermore, the device has a maximum efficiency of 55%, so its actual COP is much lower than this calculated value. However, regardless of these losses, the effective COP is still significantly higher than a conventional cooling system, even if water must first be purified by desalination. In areas where water is not available in any form, it can be used with a desiccant to recover water using available heat sources, such as solar thermal energy.[21][22]

Theoretical designs

edit

In the newer but yet-to-be-commercialized "cold-SNAP" design from Harvard's Wyss Institute, a 3D-printed ceramic conducts heat but is half-coated with a hydrophobic material that serves as a moisture barrier.[23] While no moisture is added to the incoming air the relative humidity (RH) does rise a little according to the Temperature-RH formula. Still, the relatively dry air resulting from indirect evaporative cooling allows inhabitants' perspiration to evaporate more easily, increasing the relative effectiveness of this technique. Indirect Cooling is an effective strategy for hot-humid climates that cannot afford to increase the moisture content of the supply air due to indoor air quality and human thermal comfort concerns.

Passive indirect evaporative cooling strategies are rare because this strategy involves an architectural element to act as a heat exchanger (for example a roof). This element can be sprayed with water and cooled through the evaporation of the water on this element. These strategies are rare due to the high use of water, which also introduces the risk of water intrusion and compromising building structure.

Hybrid designs

edit

Two-stage evaporative cooling, or indirect-direct

edit

In the first stage of a two-stage cooler, warm air is pre-cooled indirectly without adding humidity (by passing inside a heat exchanger that is cooled by evaporation on the outside). In the direct stage, the pre-cooled air passes through a water-soaked pad and picks up humidity as it cools. Since the air supply is pre-cooled in the first stage, less humidity is transferred in the direct stage, to reach the desired cooling temperatures. The result, according to manufacturers, is cooler air with a RH between 50 and 70%, depending on the climate, compared to a traditional system that produces about 70–80% relative humidity in the conditioned air.

Evaporative + conventional backup

edit

In another hybrid design, direct or indirect cooling has been combined with vapor-compression or absorption air conditioning to increase the overall efficiency and/or to reduce the temperature below the wet-bulb limit.

Evaporative + passive daytime radiative + thermal insulation

edit

Evaporative cooling can be combined with passive daytime radiative cooling and thermal insulation to enhance cooling power with zero energy use, albeit with an occasional water "re-charge" depending on the climatic zone of the installation. The system, developed by Lu et al. "consists of a solar reflector, a water-rich and IR-emitting evaporative layer, and a vapor-permeable, IR-transparent, and solar-reflecting insulation layer," with the top layer enabling "heat removal through both evaporation and radiation while resisting environmental heating." The system demonstrated 300% higher ambient cooling power than stand-alone passive daytime radiative cooling and could extend the shelf life of food by 40% in cool humid climates and 200% in dry climates without refrigeration.[24]

Membrane dehumidification and evaporative cooling

edit

Conventional evaporative cooling only works with dry air, e.g. when the humidity ratio is below ~0.02 kgwater/kgair.[25] They also require substantial water inputs. To remove these limitations, dewpoint evaporative cooling can be hybridized with membrane dehumidification, using membranes that pass water vapor but block air.[25] Air passing through these membranes can be concentrated with a compressor, so it can be condensed at warmer temperatures. The first configuration with this approach reused the dehumidification water to provide further evaporative cooling. Such an approach can fully provide its own water for evaporative cooling, outperforms a baseline desiccant wheel system under all conditions, and outperforms vapor compression in dry conditions. It can also allow for cooling at higher humidity without the use of refrigerants, many of which have substantial greenhouse gas potential.[25]

Materials

edit

Traditionally, evaporative cooler pads consist of excelsior (aspen wood fiber) inside a containment net, but more modern materials, such as some plastics and melamine paper, are entering use as cooler-pad media. Modern rigid media, commonly 8" or 12" thick, adds more moisture, and thus cools air more than typically much thinner aspen media.[26] Another material which is sometimes used is corrugated cardboard.[27][28]

Design considerations

edit

Water use

edit

In arid and semi-arid climates, the scarcity of water makes water consumption a concern in cooling system design. From the installed water meters, 420938 L (111,200 gal) of water were consumed during 2002 for the two passive cooling towers at the Zion National Park visitors' center.[29] However, such concerns are addressed by experts who note that electricity generation usually requires a large amount of water, and evaporative coolers use far less electricity, and thus comparable water overall, and cost less overall, compared to chillers.[30]

Shading

edit

Allowing direct solar exposure to any surface which can transfer the extra heat to any part of the air flow through the unit will raise the temperature of the air. If the heat is transferred to the air prior to flowing through the pads, or if the sunlight warms the pads themselves, evaporation will increase, but the additional energy required to achieve this will not come from the energy contained in the ambient air, but will be supplied by the sun, and this will result not only in higher temperatures, but higher humidity as well, just as raising the inlet air temperature by any means, and heating the water prior to distribution over the pad by any means, would do. In addition, sunlight may degrade some media, and other components of the cooler. Therefore, shading is advisable in all circumstances, though the vertical aspect of the pads, and insulation between the exterior and interior horizontal (upwards facing) surfaces to minimise heat transfer will suffice.

Mechanical systems

edit

Apart from fans used in mechanical evaporative cooling, pumps are the only other piece of mechanical equipment required for the evaporative cooling process in both mechanical and passive applications. Pumps can be used for either recirculating the water to the wet media pad or providing water at very high pressure to a mister system for a passive cooling tower. Pump specifications will vary depending on evaporation rates and media pad area. The Zion National Park visitors' center uses a 250 W (1/3 HP) pump.[31]

Exhaust

edit

Exhaust ducts and/or open windows must be used at all times to allow air to continually escape the air-conditioned area. Otherwise, pressure develops and the fan or blower in the system is unable to push much air through the media and into the air-conditioned area. The evaporative system cannot function without exhausting the continuous supply of air from the air-conditioned area to the outside. By optimizing the placement of the cooled-air inlet, along with the layout of the house passages, related doors, and room windows, the system can be used most effectively to direct the cooled air to the required areas. A well-designed layout can effectively scavenge and expel the hot air from desired areas without the need for an above-ceiling ducted venting system. Continuous airflow is essential, so the exhaust windows or vents must not restrict the volume and passage of air being introduced by the evaporative cooling machine. One must also be mindful of the outside wind direction, as, for example, a strong hot southerly wind will slow or restrict the exhausted air from a south-facing window. It is always best to have the downwind windows open, while the upwind windows are closed.

Different types of installations

edit

Typical installations

edit

Typically, residential and industrial evaporative coolers use direct evaporation, and can be described as an enclosed metal or plastic box with vented sides. Air is moved by a centrifugal fan or blower (usually driven by an electric motor with pulleys known as "sheaves" in HVAC terminology, or a direct-driven axial fan), and a water pump is used to wet the evaporative cooling pads. The cooling units can be mounted on the roof (down draft, or downflow) or exterior walls or windows (side draft, or horizontal flow) of buildings. To cool, the fan draws ambient air through vents on the unit's sides and through the damp pads. Heat in the air evaporates water from the pads which are constantly re-dampened to continue the cooling process. Then cooled, moist air is delivered into the building via a vent in the roof or wall.

Because the cooling air originates outside the building, one or more large vents must exist to allow air to move from inside to outside. Air should only be allowed to pass once through the system, or the cooling effect will decrease. This is due to the air reaching the saturation point. Often 15 or so air changes per hour (ACHs) occur in spaces served by evaporative coolers, a relatively high rate of air exchange.

Evaporative (wet) cooling towers

edit
 
Large hyperboloid cooling towers made of structural steel for a power plant in Kharkіv (Ukraine)

Cooling towers are structures for cooling water or other heat transfer media to near-ambient wet-bulb temperature. Wet cooling towers operate on the evaporative cooling principle, but are optimized to cool the water rather than the air. Cooling towers can often be found on large buildings or on industrial sites. They transfer heat to the environment from chillers, industrial processes, or the Rankine power cycle, for example.

Misting systems

edit
 
Mist spraying system with water pump beneath

Misting systems work by forcing water via a high pressure pump and tubing through a brass and stainless steel mist nozzle that has an orifice of about 5 micrometres, thereby producing a micro-fine mist. The water droplets that create the mist are so small that they instantly flash-evaporate. Flash evaporation can reduce the surrounding air temperature by as much as 35 °F (20 °C) in just seconds.[32] For patio systems, it is ideal to mount the mist line approximately 8 to 10 feet (2.4 to 3.0 m) above the ground for optimum cooling. Misting is used for applications such as flowerbeds, pets, livestock, kennels, insect control, odor control, zoos, veterinary clinics, cooling of produce, and greenhouses.

Misting fans

edit

A misting fan is similar to a humidifier. A fan blows a fine mist of water into the air. If the air is not too humid, the water evaporates, absorbing heat from the air, allowing the misting fan to also work as an air cooler. A misting fan may be used outdoors, especially in a dry climate. It may also be used indoors.

Small portable battery-powered misting fans, consisting of an electric fan and a hand-operated water spray pump, are sold as novelty items. Their effectiveness in everyday use is unclear.[citation needed]

Performance

edit

Understanding evaporative cooling performance requires an understanding of psychrometrics. Evaporative cooling performance is variable due to changes in external temperature and humidity level. A residential cooler should be able to decrease the temperature of air to within 3 to 4 °C (5 to 7 °F) of the wet bulb temperature.

It is simple to predict cooler performance from standard weather report information. Because weather reports usually contain the dewpoint and relative humidity, but not the wet-bulb temperature, a psychrometric chart or a simple computer program must be used to compute the wet bulb temperature. Once the wet bulb temperature and the dry bulb temperature are identified, the cooling performance or leaving air temperature of the cooler may be determined.

For direct evaporative cooling, the direct saturation efficiency,  , measures in what extent the temperature of the air leaving the direct evaporative cooler is close to the wet-bulb temperature of the entering air. The direct saturation efficiency can be determined as follows:[33]

 
Where:
  = direct evaporative cooling saturation efficiency (%)
  = entering air dry-bulb temperature (°C)
  = leaving air dry-bulb temperature (°C)
  = entering air wet-bulb temperature (°C)

Evaporative media efficiency usually runs between 80% and 90%. Most efficient systems can lower the dry air temperature to 95% of the wet-bulb temperature, the least efficient systems only achieve 50%.[33] The evaporation efficiency drops very little over time.

Typical aspen pads used in residential evaporative coolers offer around 85% efficiency while CELdek[further explanation needed] type of evaporative media offer efficiencies of >90% depending on air velocity. The CELdek media is more often used in large commercial and industrial installations.

As an example, in Las Vegas, with a typical summer design day of 42 °C (108 °F) dry bulb and 19 °C (66 °F) wet bulb temperature or about 8% relative humidity, the leaving air temperature of a residential cooler with 85% efficiency would be:

  = 42 °C – [(42 °C – 19 °C) × 85%] = 22.45 °C or 72.41 °F

However, either of two methods can be used to estimate performance:

  • Use a psychrometric chart to calculate wet bulb temperature, and then add 5–7 °F as described above.
  • Use a rule of thumb which estimates that the wet bulb temperature is approximately equal to the ambient temperature, minus one third of the difference between the ambient temperature and the dew point. As before, add 5–7 °F as described above.

Some examples clarify this relationship:

  • At 32 °C (90 °F) and 15% relative humidity, air may be cooled to nearly 16 °C (61 °F). The dew point for these conditions is 2 °C (36 °F).
  • At 32 °C and 50% relative humidity, air may be cooled to about 24 °C (75 °F). The dew point for these conditions is 20 °C (68 °F).
  • At 40 °C (104 °F) and 15% relative humidity, air may be cooled to nearly 21 °C (70 °F). The dew point for these conditions is 8 °C (46 °F).

(Cooling examples extracted from the June 25, 2000 University of Idaho publication, "Homewise").

Because evaporative coolers perform best in dry conditions, they are widely used and most effective in arid, desert regions such as the southwestern USA, northern Mexico, and Rajasthan.

The same equation indicates why evaporative coolers are of limited use in highly humid environments: for example, a hot August day in Tokyo may be 30 °C (86 °F) with 85% relative humidity, 1,005 hPa pressure. This gives a dew point of 27.2 °C (81.0 °F) and a wet-bulb temperature of 27.88 °C (82.18 °F). According to the formula above, at 85% efficiency air may be cooled only down to 28.2 °C (82.8 °F) which makes it quite impractical.

Comparison to other types of air conditioning

edit
 
A misting fan

Comparison of evaporative cooling to refrigeration-based air conditioning:

Advantages

edit

Less expensive to install and operate

  • Estimated cost for professional installation is about half or less that of central refrigerated air conditioning.[34]
  • Estimated cost of operation is 1/8 that of refrigerated air conditioning.[35]
  • No power spike when turned on due to lack of a compressor.
  • Power consumption is limited to the fan and water pump, which have a relatively low current draw at start-up.
  • The working fluid is water. No special refrigerants, such as ammonia or CFCs, are used that could be toxic, expensive to replace, contribute to ozone depletion and/or be subject to stringent licensing and environmental regulations.
  • Newly launched air coolers can be operated though remote control.[36]

Ease of installation and maintenance

  • Equipment can be installed by mechanically-inclined users at drastically lower cost than refrigeration equipment which requires specialized skills and professional installation.
  • The only two mechanical parts in most basic evaporative coolers are the fan motor and the water pump, both of which can be repaired or replaced at low cost and often by a mechanically inclined user, eliminating costly service calls to HVAC contractors.

Ventilation air

  • The frequent and high volumetric flow rate of air traveling through the building reduces the "age-of-air" in the building dramatically.
  • Evaporative cooling increases humidity. In dry climates, this may improve comfort and decrease static electricity problems.
  • The pad itself acts as a rather effective air filter when properly maintained; it is capable of removing a variety of contaminants in air, including urban ozone caused by pollution, [citation needed] regardless of very dry weather. Refrigeration-based cooling systems lose this ability whenever there is not enough humidity in the air to keep the evaporator wet while providing a frequent trickle of condensation that washes out dissolved impurities removed from the air.

Disadvantages

edit

Performance

  • Most evaporative coolers are unable to reach as low a temperature as refrigerated air conditioning systems.
  • High dewpoint (humidity) conditions decrease the cooling capability of the evaporative cooler.
  • No dehumidification. Traditional air conditioners remove moisture from the air, except in very dry locations where recirculation can lead to a buildup of humidity. Evaporative cooling adds moisture, and in humid climates, dryness may improve thermal comfort at higher temperatures.

Comfort

  • The air supplied by the evaporative cooler is generally 80–90% relative humidity and can cause interior humidity levels as high as 65%; very humid air reduces the evaporation rate of moisture from the skin, nose, lungs, and eyes.
  • High humidity in air accelerates corrosion, particularly in the presence of dust. This can considerably reduce the life of electronics and other equipment.
  • High humidity in air may cause condensation of water. This can be a problem for some situations (e.g., electrical equipment, computers, paper, books, old wood).
  • Odors and other outdoor contaminants may be blown into the building unless sufficient filtering is in place.

Water use

  • Evaporative coolers require a constant supply of water.
  • Water high in mineral content (hard water) will leave mineral deposits on the pads and interior of the cooler. Depending on the type and concentration of minerals, possible safety hazards during the replacement and waste removal of the pads could be present. Bleed-off and refill (purge pump) systems can reduce but not eliminate this problem. Installation of an inline water filter (refrigerator drinking water/ice maker type) will drastically reduce the mineral deposits.

Maintenance frequency

  • Any mechanical components that can rust or corrode need regular cleaning or replacement due to the environment of high moisture and potentially heavy mineral deposits in areas with hard water.
  • Evaporative media must be replaced on a regular basis to maintain cooling performance. Wood wool pads are inexpensive but require replacement every few months. Higher-efficiency rigid media is much more expensive but will last for a number of years proportional to the water hardness; in areas with very hard water, rigid media may only last for two years before mineral scale build-up unacceptably degrades performance.
  • In areas with cold winters, evaporative coolers must be drained and winterized to protect the water line and cooler from freeze damage and then de-winterized prior to the cooling season.

Health hazards

  • An evaporative cooler is a common place for mosquito breeding. Numerous authorities consider an improperly maintained cooler to be a threat to public health.[37]
  • Mold and bacteria may be dispersed into interior air from improperly maintained or defective systems, causing sick building syndrome and adverse effects for asthma and allergy sufferers. This can also cause a foul odor.
  • Wood wool of dry cooler pads can catch fire even from small sparks.

See also

edit

References

edit
  1. ^ Kheirabadi, Masoud (1991). Iranian cities: formation and development. Austin, TX: University of Texas Press. p. 36. ISBN 978-0-292-72468-6.
  2. ^ Zellweger, John (1906). "Air filter and cooler". U.S. patent 838602. Archived from the original on January 24, 2013.
  3. ^ Essick, Bryant (1945). "Pad for evaporative coolers". U.S. patent 2391558.
  4. ^ Landis, Scott (1998). The Workshop Book. Taunton Press. p. 120. ISBN 978-1-56158-271-6. evaporative cooler squirrel cage southwest popular.
  5. ^ Gutenberg, Arthur William (1955). The Economics of the Evaporative Cooler Industry in the Southwestern United States. Stanford University Graduate School of Business. p. 167.
  6. ^ Such units were mounted on the passenger-side window of the vehicle; the window was rolled nearly all the way up, leaving only enough space for the vent which carried the cool air into the vehicle.
  7. ^ a b c Givoni, Baruch (1994). Passive and Low-Energy Cooling of Buildings. Van Nostrand Reinhold.
  8. ^ McDowall, R. (2006). Fundamentals of HVAC Systems, Elsevier, San Diego, page 16.
  9. ^ Cryer, Pat. "Food storage in a working class London household in the 1900s". 1900s.org.uk. Retrieved 22 November 2013.
  10. ^ Bonan, Gordon B. (13 June 2008). "Forests and Climate Change: Forcings, Feedbacks, and the Climate Benefits of Forests". Science. 320 (5882): 1444–9. Bibcode:2008Sci...320.1444B. doi:10.1126/science.1155121. PMID 18556546. S2CID 45466312.
  11. ^ Verploegen, Eric; Rinker, Peter; Ognakossan, Kukom Edoh. "Evaporative Cooling Best Practices Guide" (PDF).
  12. ^ Verploegen, Eric; Sanogo, Ousmane; Chagomoka, Takemore. "Evaporative Cooling Technologies for Improved Vegetable Storage in Mali - Evaluation" (PDF).
  13. ^ Peck, John F.; Kessler, Helen J.; Lewis, Thompson L. (1979). "Monitoring, Evaluating, & Optimizing Two Stage Evaporative Cooling Techniques". Environmental Research Laboratory, University of Arizona.
  14. ^ Kwok, Alison G.; Grondzik, Walter T. (2007). The green studio handbook: environmental strategies for schematic design. Architectural Press. ISBN 978-0-08-089052-4.
  15. ^ Grondzik, Walter T.; Kwok, Alison G.; Stein, Benjamin; Reynolds, John S. (2010). Mechanical and Electrical Equipment. John Wiley & Sons.
  16. ^ Energy Information Administration. "Annual Energy Review 2004". EIA. U.S. Department of Energy. Retrieved 12 December 2014.
  17. ^ Maheshwari, G.P.; Al-Ragom, F.; Suri, R.K. (2001). "Energy-saving potential of an indirect evaporative cooler". Applied Energy. 69 (1): 69–76. Bibcode:2001ApEn...69...69M. doi:10.1016/S0306-2619(00)00066-0.
  18. ^ see Independent Testing tab, Thermodynamic performance assessment of a novel air cooling cycle and other papers http://www.coolerado.com/products/material-resource-center/
  19. ^ Coolerado Cooler Helps to Save Cooling Energy and Dollars: New Cooling Technology Targets Peak Load Reduction; Robichaud, R; 2007; https://www.osti.gov/biblio/908968-coolerado-cooler-helps-save-cooling-energy-dollars-new-cooling-technology-targets-peak-load-reduction
  20. ^ "Coolerado Chills Snow & Ice Data Center". Data Center Knowledge. August 12, 2011.
  21. ^ Maisotsenko cycle based counter and cross flow heat and mass exchanger: A computational study. 2017 International Conference on Energy Conservation and Efficiency (ICECE). Rasikh Tariq; Nadeem Ahmed Sheikh: 2017, pp. 44–49
  22. ^ Maisotsenko cycle: technology overview and energy-saving potential in cooling systems. Journal of Energy and Emission Control Technologies. 6 March 2015 Volume 2015:3 pp. 15–22. Emmanuel D Rogdakis, Dimitrios Nik Tertipis. Faculty of Mechanical Engineering, National Technical University of Athens, Athens, Greece
  23. ^ "cold-SNAP: Eco-friendly air conditioning". Wyss Institute. 27 September 2019.
  24. ^ Lu, Zhengmao; Leroy, Arny; Zhang, Lenan; Patel, Jatin J.; Wang, Evelyn N.; Grossman, Jeffrey C. (September 2022). "Significantly enhanced sub-ambient passive cooling enabled by evaporation, radiation, and insulation". Cell Reports Physical Science. 3 (10): 101068. Bibcode:2022CRPS....301068L. doi:10.1016/j.xcrp.2022.101068. hdl:1721.1/146578. S2CID 252411940.
  25. ^ a b c Mumtaz, Maisha; Pamintuan, Bryan C.; Fix, Andrew J.; Braun, James E.; Warsinger, David M. (2023). "Hybrid membrane dehumidification and dewpoint evaporative cooling for sustainable air conditioning". Energy Conversion and Management. 294. Elsevier BV: 117547. Bibcode:2023ECM...29417547M. doi:10.1016/j.enconman.2023.117547. ISSN 0196-8904. S2CID 261440235.
  26. ^ https://web.archive.org/web/20170106124739/http://www.pge.com/includes/docs/pdfs/myhome/saveenergymoney/savingstips/evap/eedectechsheet.pdf. Archived from the original (PDF) on 2017-01-06. Retrieved 2015-07-14. {{cite web}}: Missing or empty |title= (help)
  27. ^ Margolis, Jonathan (24 November 2012). "Corrugated cardboard swamp cooler by Sundrop Farm". Theguardian.com. Retrieved 2018-09-25.
  28. ^ "Sundrop Farm's system". Sundropfarms.com. 2014-06-20. Retrieved 2018-09-25.
  29. ^ Torcellini, P; Long, N; Pless, S; Judkoff, R (February 2005). Evaluation of the Low-Energy Design and Energy Performance of the Zion National Park Visitors Center – Technical Report NREL/TP-550-34607 (PDF). p. 88. Retrieved 9 June 2020.
  30. ^ "Evaporative Cooling Design Guidelines Manual for New Mexico Schools and Commercial Buildings" (PDF). December 2002. pp. 25–27. Retrieved 12 September 2015.
  31. ^ Torcellini, P.; Pless, S.; Deru, M.; Long, N.; Judkoff, R. (2006). Lessons Learned from Case Studies of Six High-Performance Buildings – Technical Report NREL/TP-550-37542 (PDF).
  32. ^ [1] Archived May 18, 2007, at the Wayback Machine
  33. ^ a b HVAC Systems and Equipment (SI ed.). Atlanta, GA: American Society of Heating Refrigeration and Air-conditioning Engineers (ASHRAE). 2012. p. 41.1.
  34. ^ Krigger, John; Dorsi, Chris (2004). Residential Energy: Cost Savings and Comfort for Existing Buildings (4th ed.). Saturn Resource Management. p. 207. ISBN 978-1-880120-12-5.[permanent dead link]
  35. ^ "Evaporative cooler/ Evaporative cooler". Waterlinecooling.com. Archived from the original on 2013-12-02. Retrieved 2013-11-22.
  36. ^ "Latest technology stylish looks and compact build". bonafideresearch.com. Retrieved 2021-08-04.
  37. ^ "A brief note on the NID Cooler" (PDF). Government of India - National Centre for Disease Control. Archived from the original (PDF) on 10 October 2017. Retrieved 22 November 2013.
edit