Thermostatic mixing valve

(Redirected from Mixing valve)

A thermostatic mixing valve (TMV) is a valve that blends hot water with cold water to ensure constant, safe shower and bath outlet temperatures to prevent scalding.

Thermostatbatterie = thermostatic mixing valve
WW-Zulauf = Warmwasser-Zulauf = Hot water input
KW-Zulauf = Kaltwasser-Zulauf = Cold water input
Temperaturregler =Temperature regulator
Abgang = Outlet
Mengeneinstellung = Volume control

The storage of water at high temperature removes one possible breeding ground for Legionella; the use of a thermostat, rather than a static mixing valve, provides increased safety against scalding, and increased user comfort, because the hot-water temperature remains constant.[1]

Many TMVs use a wax thermostat for regulation. They also shut off rapidly in the event of a hot or cold supply failure to prevent scalding or thermal shock.

It is increasingly common practice around the world to regulate the storage water temperature to above 60 °C (140 °F), and to circulate or distribute water at a temperature less than 50 °C (122 °F). Water above these temperatures can cause scald injuries. Many countries, states, or municipalities now require that the temperature of all bath water in newly built and extensively refurbished domestic properties be controlled to a maximum of 48 °C (118 °F). Installing thermostatic mixing valves can ensure that water is delivered at the required temperature, thereby reducing the risk of scalding accidents; it also reduces hot water consumption from a supply that is maintained at a higher temperature.[2]

There are three main categories for water temperature controlling devices: Heat Source, Group Control, and Point-of-Use.

Heat Source

These are used with central heating systems that use water as a medium.

  • Tempering valves for use on hot water heat distribution systems
  • High flow rates suitable for use in under floor (radiant) heating applications
  • Allows water to be stored at a higher temperature
Group Control

These provide a uniform distribution temperature for all hot water outlets in a household.

  • Designed for multi-point applications
  • High flow rates (from 14 to 51 US gallons per minute (53 to 193 L/min) at 45 pounds per square inch (3.1 bar))
  • Temperature stability
Point-of-Use

These are single Outlet Thermostatic Mixing Valves, often called "thermostatic faucets", "thermostat taps" or "thermostat valves".

  • Designed for single point applications, such as individual showering, hand wash basin mixers, bath or tub fillers
  • High level protection against scalding and thermal shock

Although other temperature regulating valves exist, thermostatic mixing valves are the preferred type in health care facilities, as they limit maximum outlet temperature, regardless of pressure or flow.

See also

edit

References

edit
  1. ^ "Thermostatic mixing valve". Heating/Piping/Air Conditioning Engineering. 84 (1). 2012.
  2. ^ "Thermostatic mixing valve". Heating/Piping/Air Conditioning Engineering. 83 (10). 2011-10-26.
edit